Engineers inspecting industrial machinery where PyXis vibration sensor mounting location and rigidity affect repeatable measurements

A three-axis vibration sensor measures three directions at its mounting point. A second mounting point answers a different question: how the housing moves at the other end of the motor. A trend taken beside the coupling can help a team investigate the drive end. A trend taken at the opposite bearing can reveal how differently that end responds under the same operating condition. Record the location as carefully as the direction.

Choose the bearing locations before choosing the channels

Mark the drive end and non-drive end on the asset drawing. On a coupled motor, the drive end normally sits next to the coupling. Check the machine drawing before using the same label on an unusual drive arrangement. Identify a rigid mounting surface near each bearing and confirm the approved method with the motor maker and site team. A shroud, a fan cover or a flexible bracket can move independently of the bearing housing. Compare mounting positions with a reference instrument if the preferred point is inaccessible.

Start with one fixed sensor if the maintenance team has a clearly defined monitoring target and can regularly cover the other end with a repeatable route measurement. Include both ends when the bearings have different access, duty or failure consequences, when the two ends already behave differently, or when technicians cannot reliably take the second reading during production. For a motor and pump or gearbox, record positions on the driven equipment separately. A motor drive-end tag does not identify a pump bearing.

Map the axes and keep the two readings comparable

Draw an arrow along the shaft for the axial direction and mark the two orthogonal radial directions at each sensor. A vertical motor does not use the same physical reference as a horizontal machine. Record mounting orientation, method and surface condition, then photograph each point. If a sensor or bracket moves after maintenance, establish a new comparison baseline or document how the change affects the existing trend. Keep the point name, physical axis, units and measurement type in the controller and historian tags.

Compare the two points under a common operating state. Record speed, load and time alongside vibration. For a variable-speed motor, group samples by documented speed and load ranges so a normal production change does not look like a bearing trend. Use comparable time windows for condition trends. For phase or transient analysis, select instruments and acquisition that provide a shared timing reference and verify it explicitly. A PLC poll timestamp identifies when the PLC read a value; check the acquisition timing separately.

Run a short acceptance test before handover

  1. Match each physical label to its PLC or historian tag and confirm the displayed axes, units and measurement type against the delivered configuration.
  2. At a stable operating point, record both locations and repeat the measurements. Use a portable reference on an adjacent approved point if you need a cross-check. Agree site tolerances before interpreting the comparison.
  3. In a safe test environment, simulate unavailable or stale data for one sensor. Verify that the screen marks the affected point as unavailable and preserves the other point.
  4. Save the baseline, operating state, mounting photos and sensor identities. Define which team investigates a change and where it will check first.

For PyXis integration, use the controlled PyXis 222x datasheet TTN-DS-2026-002, Rev 08 and the register map issued for the installed firmware. Resolve field definitions against the delivered device before mapping PLC tags. Yokogawa’s Sushi Sensor application note provides an independent example of selecting vibration measurement points for different monitoring targets.

See the PyXis product guide or send Tachyonic your motor layout to discuss measurement points. Illustrative photograph: abdo alshreef / Pexels, Pexels licence. The photograph shows maintenance work, not a PyXis installation.